The physical, electrical, and environmental specifications for the Challenge rackmount server are listed in Table A-1.
Table A-1. Challenge Rackmount Server Specifications
Parameter | Characteristics |
---|---|
Enclosure |
|
Dimensions | 27”w (69 cm) x 48”d (122 cm) x 62.3”h (159 cm) |
Weight | 560 lbs (254 kg), base configuration |
Lower vertical opening | 23 inches (58 cm) |
Total vertical opening | 56 inches (124 cm) |
Minimum Clearance |
|
Left side | 33 inches (84 cm) |
Right side | 36 inches (91.4 cm) |
Rear panel door | 42 inches (106.7 cm) |
Front | 37 inches (94 cm) |
Electrical |
|
Voltage | 208-240VAC |
Frequency | 47-63 Hz, single phase |
Current | 30 amps, maximum |
Power | 5700 watts, maximum |
Power supply | 1900 watts, 1-3 Offline switchers |
Temperature |
|
Operating | 15o to 35oC |
Nonoperating | –40o to 50oC |
Humidity |
|
Operating | 20 to 80% relative humidity, noncondensing |
Nonoperating | 20 to 95% relative humidity, noncondensing |
Thermal output | 600 Btu/hr, maximum |
Heat dissipation | 10,900 Btu/hr chassis |